Residential Heat Recovery
MRXBOX90
MRXBOX70
LPXBOXDC-2
COOKERXBOX
Multi Point Extract
MEVAC and MEVDC
MEV-SVS
Genie
Positive Input Ventilation
Drimaster
Drimaster 2000
Drimaster 365
Flatmaster
Flatmaster 2000
Renewables
Sunwarm Tile
Sunwarm Air
Sunwarm
Sunwarm Heat Recovery
Sunwarm Hot Water
Air Handling Units
Ecosmart Boxer
Commercial Heat Recovery
Squrbo Xbox Horizontal
Squrbo Xbox Stacked
Squrbo Xbox Twinfan
Opus Xbox
Ecostrat
Supply & Extract
Opus 40-60-95
Opus DC
Opus Plus
XS
Squrbo
Ecosmart Squrbo Extract
Ecosmart Squrbo Supply
Xtractor
Xtractor Constant Pressure
Airmover
Squif
Twin Fans
Opus 40-60-95
Opus DC
Opus Plus
Quietscroll
Quietscroll Constant Pressure
Squif Twin
Axial Fans
Axus
Axus Bifurcated
EZPLATE
Smoke Fans
SVT Axial Impulse
SVT Centrifugl Impulse
HT Axus
HT Squif
Roof Fans
Terminator
Mark Ten

Opus Plus Product Specifications

Operation
The extract fans shall be as indicated on the drawings and shall be in accordance with the particular fan schedule in this specification. The vitiated air shall be extracted from each area via ductwork as shown. All necessary ductwork fittings and ancillaries shall be allowed for by the mechanical sub contractor. The extract fans shall be operated as it receives signals from one of the interconnected sensors or an external signal e.g. lightswitch. The OPUS plus shall have the facility to increase speed on a trickle and boost principle when triggered.

General Fan specification
The fans are acoustically lined with high density class “O” flame retardant acoustic insulation, giving extremely low noise levels and shall be complete with an integral filter (surface mounted versions only); integral controls, magnetic backdraught shutters and facia mounted run and fail indication. The breakout noise level and power requirements in accordance with the schedule and the manufacturer’s details. The fans shall have low energy, high efficiency fan/motor assembly with sealed for life bearings.

Opus Plus
The unit shall be supplied complete with automatic fan changeover in the event of failure, sensed via a “hall effect” airflow sensor, and auto duty share every 12 hours of run time.

Duct Mounted
The unit shall incorporate a low profile single point mounting bracket, incorporating a pre-stressed synthetic anti vibration seal. The bracket shall enable the unit to be mounted horizontally or vertically. The depth of the unit shall not be greater than 260mm. The unit shall be constructed with one removable panel allowing full maintenance access. To facilitate the interconnection of branch ducts the unit shall have 4x100 dia & 1x 125 dia knockouts on the suction side of the unit (spigots provided). Fan shall be the OPUS100- (2) M or the OPUS150-M as manufactured by Nuaire

Surface Mounted
All fan components are manufactured from flame retardant ABS polymer and pre-coated steel. Unit finish shall be white.
Fan to have the option of an integrated PIR detector to switch the unit from trickle or off to full speed. Fans complete with integrated magnetic backdraught shutters. Air inlet grilles are fitted with foam filters to protect the fan/motor assembly from airborne dust and contaminants. The unit shall have a 125dia spigot to connect to ductwork or wall mounting kit. Surface mounted LED indicators shall show the unit operational status.
The unit shall be supplied complete with automatic fan changeover in the event of failure, sensed via a “hall effect” airflow sensor, and auto duty share every 12 hours of run time.

All versions shall have the following functions integrally mounted within the fan unit on a purpose made PCB, all such components pre-wired and factory fitted by the manufacturer: -
  • Integral adjustable background ventilation control/set point (0 – 50%)
  • Integral adjustable trickle ventilation control/set point (50 – 100%)
  • Integral adjustable run on timer.
  • Integral S/L terminal for boost trigger from remote switch, e.g. lightswitch.
  • Integral low voltage terminal for boost trigger from remote low voltage switch
  • Volt free failure/status indication.
  • 3 years manufacturers warranty
The unit shall be controlled by one of the following remote options
  • OPUS –SPD – Low voltage (12v) speed control, ON/OFF and speed control between min and max settings.
  • 230-PIR - (passive infra-red) movement detector (includes run-on timer), 2-30 mins).
  • 230-PIRNT - (passive infra-red) movement detector (without run-on timer)
  • HUMISEN - Humidity sensor.
  • 230-TSTATR – Room thermostat
  • CT- AVI – Remote failure indication

Fan shall be the OPUS100- 2 B or M or the OPUS150- B or M as manufactured by Nuaire Ltd

Opus 30 and 60
The fan shall be of the OPUS type supplied complete with automatic fan changeover in the event of failure, fan failure is sensed via a “hall effect” airflow sensor. The unit shall also have integrated magnetic backdraught shutters, pre-configured control module.

The control module and blower assembly shall be provided in a maintenance friendly single module, with quick release clips. The fan motors shall be thermally protected.
The surface mounted version shall have run and failure indication on the facia of the unit (RA and BA versions).
The 12v version shall come complete with 230 – 12 volt transformer.

Fan control option
The fan shall be controlled by one of the following integrated options
  • S version – Fan will run at full speed and will run on for a pre-set time (2 – 30 mins) when switched off
  • X version – Continuous run at pre-set low speed with boost to high speed via switch live connection e.g. lightswitch (Opus 30)
  • RA/BA – Failure indication on facia of unit.
The fan shall be controlled by one of the following remote options
  • 230-PIR - (passive infra-red) movement detector (includes run-on timer), 2-30 mins).
  • 230-PIRNT - (passive infra-red) movement detector (without run-on timer)
  • HUMISEN - Humidity sensor.
  • 230-TSTATR – Room thermostat
  • OPUS- RFI – Remote failure indication
  • 3 years manufacturers warranty

Fan shall be the OPUS 30 or 60 twinfan as manufactured by Nuaire Ltd

The manufacturer’s recommendations should be observed at all times.