Residential Heat Recovery
MRXBOX90
MRXBOX70
LPXBOXDC-2
COOKERXBOX
Multi Point Extract
MEVAC and MEVDC
MEV-SVS
Genie
Positive Input Ventilation
Drimaster
Drimaster 2000
Drimaster 365
Flatmaster
Flatmaster 2000
Renewables
Sunwarm Tile
Sunwarm Air
Sunwarm
Sunwarm Heat Recovery
Sunwarm Hot Water
Air Handling Units
Ecosmart Boxer
Commercial Heat Recovery
Squrbo Xbox Horizontal
Squrbo Xbox Stacked
Squrbo Xbox Twinfan
Opus Xbox
Ecostrat
Supply & Extract
Opus 40-60-95
Opus DC
Opus Plus
XS
Squrbo
Ecosmart Squrbo Extract
Ecosmart Squrbo Supply
Xtractor
Xtractor Constant Pressure
Airmover
Squif
Twin Fans
Opus 40-60-95
Opus DC
Opus Plus
Quietscroll
Quietscroll Constant Pressure
Squif Twin
Axial Fans
Axus
Axus Bifurcated
EZPLATE
Smoke Fans
SVT Axial Impulse
SVT Centrifugl Impulse
HT Axus
HT Squif
Roof Fans
Terminator
Mark Ten

MTX Product Specifications

Air Handling Unit specification
The Air Handling Unit shall be configured and arranged as detailed on the drawings and in accordance with the schedule of equipment. The units shall be manufactured from a highly rigid pentapost framework with 25mm double skinned infill panels. The panels shall contain inert high density infill. Panel materials are heavy gauge Aluzinc corrosion resistant steel. The units shall provide exceptional thermal and acoustic insertion. The general construction is to class A leakage.

The fan impeller and motor shall be selected to provide the most energy efficient solution conforming to part L regulations and shall be direct or belt drive with EFF2 high efficiency motors to BS5000 as standard. The fan impeller shall be a high efficiency forward or backward curved centrifugal design, manufactured in galvanised steel.

The contractor shall allow for all necessary ductwork transformations to and from the fan unit and any associated components in accordance with the manufacturers recommendations, DW 144 and general good practice.
  • Heating Coils - Low Pressure Hot Water
    The Low Pressure Hot Water heating coil shall be manufactured from copper tubing with high efficiency aluminium fins contained within a galvanised steel frame.
  • Heating Coils - Electric
    The Electric Heater Battery shall be factory fitted and pre-wired to an integral closed loop thyristor control. The heat output can be configured on site to suit the specific requirements.
  • Cooling Coils - Chilled Water
    The Chilled Water Coil shall be manufactured from copper tubing with high efficiency aluminium fins contained within a galvanised steel frame.
  • Cooling Coils – DX Coils
    The DX Coil shall be manufactured from copper tubing with high efficiency aluminium fins and droplet eliminator contained within a galvanised steel frame. The coil shall be filled with dry nitrogen with the pipe connections capped. It shall be factory fitted and tested by the AHU manufacturer.
  • Heat Exchanger
    The cross flow heat exchanger shall be complete with a motorised summer bypass.

The AHU shall have a 3 year warranty, first year parts and labour the remainder parts only. When the fan unit is supplied with Ecosmart controls and sensors it shall have an extended warranty. The standard warranty shall be increase from 3 to 4 years, the first year parts and labour the remainder parts only.

The unit and ancillaries shall be of the MTX type as manufactured by Nuaire Ltd

All other components shall be in accordance with the manufacturer’s specification.

Optional Control Specification
The Air Handling Unit shall be supplied with one of the following control options:-
  1. Ecosmart controls - The compact Ecosmart control system complete with all necessary controls to facilitate the operation of the ventilation system. It shall be come complete with an integral factory fitted Ecosmart PCB which will control the fan unit within the desired design parameters and provide the interface between all external control devices and the unit itself.

    The Air Handling Unit shall have the following energy saving components integrally mounted, pre-wired to interface with the purpose made PCB, all components pre-wired, configured and factory fitted by the manufacturer: -
    • Integral Frequency inverter/speed controller.
    • Integral maximum and minimum speed adjustment for commissioning.
    • Integral adjustable run on timer.
    • Integral BMS interfaces – summer/winter switching, heating control, 0-10v speed adjustment.
    • Volt free failure and status indication.
    • Integral air off temperature adjustment.
    • Facility for remote temperature control.
    • Integral background ventilation switch (trickle switch).
    • Multiple IDC sockets for interconnection of sensors or fans using pre-plugged 4-core low voltage cable.
    • Volt free frost alarm/heat demand interface.
    • Frost protection/hold off stat

    The Ecosmart controls will enable the unit to automatically vary its speed as it receives signals from one of the interconnected sensors. When the signal is received the fan shall either increase speed gradually until the required level is achieved or it will work on a trickle and boost principle. This will then and move the fan duty point from trickle/background ventilation rate to the required boost ventilation rate. Both the trickle and boost rates are infinitely variable, easy to adjust and remove the need of a main balancing damper.


The Fan unit shall have a 3 year warranty, first year parts and labour the remainder parts only. When the fan unit is supplied with Ecosmart controls and sensors it shall have an extended warranty. The standard warranty shall be increase from 3 to 4 years, the first year parts and labour the remainder parts only.

All equipment shall be as manufactured by Nuaire Ltd.