MEV Product Specifications
Apartment ventilation systemOperation
The ventilation system serving each apartment shall be designed in accordance with Approved Document F 2006 Edition (means of ventilation) of the Building Regulations 2000 for England and Wales.
The system shall enable the apartment to be adequately ventilated without the need for opening windows and thus minimising noise ingress.
The system shall consist of dedicated supply and extract units with a unique multi spigoted distribution box on the supply system, enabling each room to be individually ventilated.
The System shall operate as follows:-
The extract unit shall run continuously at a low/background ventilation rate and shall boost to a higher ventilation rate when the room being ventilated is in use, this increase shall be triggered via a manual boost switch or a “switched live” signal, typically a manual switch in the kitchen or a lightswitch. The extract unit only ventilates the “wet rooms” within the apartment i.e. bathroom, en-suite, kitchen and utility rooms.
The MEV-SVS system supplied complete with supply unit, an extract unit and a distribution box.
The units shall have a unique control system that enables the following control philosophy;
a) The extract fan will boost automatically whenever the supply is “boosted”.
b) When the extract fan is “boosted” the supply unit will only boost if it is manually “enabled” by the occupant.
The supply unit shall provide fresh filtered air continuously into all “habitable rooms” at a low/background ventilation rate and shall boost to a higher ventilation rate either when the extract fan “boosts” (if the supply unit is enabled) or when the occupant decides that a higher level of ventilation is required to ensure that a comfortable, healthy environment is maintained. In this situation the occupant will operate a manual boost switch.
There may be occasions when only extract ventilation is required; to facilitate this, the supply unit will only operate when the occupant has “enabled” the unit.
The supply and extract fans serving their respective areas shall be as indicated on the drawings and shall be in accordance with the fan schedule. The supply and vitiated air shall be extracted from each wet area via ductwork of dimensions 121x60mm and 204x60mm.
If specified the system shall be provided complete with low depth attenuators mounted adjacent to the external wall, to minimise externally generated noise ingress.
All necessary ductwork fittings and ancillaries shall be allowed for.
Supply and extract unit specification
The supply and extract units shall be manufactured to the following specification:-
The fans shall have the following control functions integrally mounted within the fan unit on a purpose made PCB, all such components pre-wired and factory fitted by the manufacturer: -
The distribution box provided with the supply unit shall be manufactured to the following specification:-
The unit shall be the MEV-SVS as manufactured by Nuaire Ductwork and ancillaries shall be Nuaire slimduct.