Residential Heat Recovery
MRXBOX90
MRXBOX70
LPXBOXDC-2
COOKERXBOX
Multi Point Extract
MEVAC and MEVDC
MEV-SVS
Genie
Positive Input Ventilation
Drimaster
Drimaster 2000
Drimaster 365
Flatmaster
Flatmaster 2000
Renewables
Sunwarm Tile
Sunwarm Air
Sunwarm
Sunwarm Heat Recovery
Sunwarm Hot Water
Air Handling Units
Ecosmart Boxer
Commercial Heat Recovery
Squrbo Xbox Horizontal
Squrbo Xbox Stacked
Squrbo Xbox Twinfan
Opus Xbox
Ecostrat
Supply & Extract
Opus 40-60-95
Opus DC
Opus Plus
XS
Squrbo
Ecosmart Squrbo Extract
Ecosmart Squrbo Supply
Xtractor
Xtractor Constant Pressure
Airmover
Squif
Twin Fans
Opus 40-60-95
Opus DC
Opus Plus
Quietscroll
Quietscroll Constant Pressure
Squif Twin
Axial Fans
Axus
Axus Bifurcated
EZPLATE
Smoke Fans
SVT Axial Impulse
SVT Centrifugl Impulse
HT Axus
HT Squif
Roof Fans
Terminator
Mark Ten

MEV Product Specifications

Apartment ventilation system

Operation
The ventilation system serving each apartment shall be designed in accordance with Approved Document F 2006 Edition (means of ventilation) of the Building Regulations 2000 for England and Wales.

The system shall enable the apartment to be adequately ventilated without the need for opening windows and thus minimising noise ingress.

The system shall consist of dedicated supply and extract units with a unique multi spigoted distribution box on the supply system, enabling each room to be individually ventilated.

The System shall operate as follows:-
The extract unit shall run continuously at a low/background ventilation rate and shall boost to a higher ventilation rate when the room being ventilated is in use, this increase shall be triggered via a manual boost switch or a “switched live” signal, typically a manual switch in the kitchen or a lightswitch. The extract unit only ventilates the “wet rooms” within the apartment i.e. bathroom, en-suite, kitchen and utility rooms.

The MEV-SVS system supplied complete with supply unit, an extract unit and a distribution box.

The units shall have a unique control system that enables the following control philosophy;
a) The extract fan will boost automatically whenever the supply is “boosted”.
b) When the extract fan is “boosted” the supply unit will only boost if it is manually “enabled” by the occupant.

The supply unit shall provide fresh filtered air continuously into all “habitable rooms” at a low/background ventilation rate and shall boost to a higher ventilation rate either when the extract fan “boosts” (if the supply unit is enabled) or when the occupant decides that a higher level of ventilation is required to ensure that a comfortable, healthy environment is maintained. In this situation the occupant will operate a manual boost switch.

There may be occasions when only extract ventilation is required; to facilitate this, the supply unit will only operate when the occupant has “enabled” the unit.

The supply and extract fans serving their respective areas shall be as indicated on the drawings and shall be in accordance with the fan schedule. The supply and vitiated air shall be extracted from each wet area via ductwork of dimensions 121x60mm and 204x60mm.

If specified the system shall be provided complete with low depth attenuators mounted adjacent to the external wall, to minimise externally generated noise ingress.

All necessary ductwork fittings and ancillaries shall be allowed for.

Supply and extract unit specification
The supply and extract units shall be manufactured to the following specification:-
  • Units shall be no deeper than 185mm.
  • Acoustic and thermal lining to provide low noise levels within the apartment and to minimise condensate formation within the units.
  • Low energy d.c. motor with advanced impeller technology. ensuring the most energy efficient installation.
  • Maximum input power 52W/fan.
  • Complete with a G4 filter.
  • Multiple spigots 4x100 diameter & 2x 125 diameter on suction side.
  • Integrated balancing dampers in each spigot connection.
  • Integrated single point mounting bracket with anti vibration strip.
  • 5 years parts and labour warrantee.
  • ISO 9002
  • The casing shall be made of Aluzinc, corrosion resistant steel conforming to BS EN 10215:1995

    The fans shall have the following control functions integrally mounted within the fan unit on a purpose made PCB, all such components pre-wired and factory fitted by the manufacturer: -
  • ‘Dial-a-Duty’ Infinitely variable constant volume / variable pressure background ventilation control.
  • ‘Dial-a-Duty’ Infinitely variable constant volume / variable pressure boost ventilation control.
  • Integral adjustable run on timer.
  • Integral S/L terminal for boost trigger from remote switch, e.g. lightswitch.
  • Integral low voltage terminal for boost trigger from kitchen (if required).
  • Automatic speed adjustment to maintain airflow in “filter dirty” conditions.
  • Volt free failure/status indication.
  • The unit can be switched to operate at the maximum flowrate setting by one of the following means.
  • Switched live signal.
  • Optional Ecosmart or Mains plug in sensor ; humidity, temperature or PIR.
  • External volt free contact (SELV signal used).
  • Please note the flowrate setting can only be achieved if the system resistance does not exceed the fan’s maximum performance.

    The distribution box provided with the supply unit shall be manufactured to the following specification:-
  • It shall be acoustically lined to minimise noise transmittance.
  • Multiple spigots 4number 121x60 and 2number 204x60.
  • It shall be no deeper than 90mm. Overall dimensions 300 x 300 x 90mm.
  • Manufactured from Aluzinc, corrosion resistant steel conforming to BS EN 10215:1995


  • The unit shall be the MEV-SVS as manufactured by Nuaire Ductwork and ancillaries shall be Nuaire slimduct.