Residential Heat Recovery
MRXBOX90
MRXBOX70
LPXBOXDC-2
COOKERXBOX
Multi Point Extract
MEVAC and MEVDC
MEV-SVS
Genie
Positive Input Ventilation
Drimaster
Drimaster 2000
Drimaster 365
Flatmaster
Flatmaster 2000
Renewables
Sunwarm Tile
Sunwarm Air
Sunwarm
Sunwarm Heat Recovery
Sunwarm Hot Water
Air Handling Units
Ecosmart Boxer
Commercial Heat Recovery
Squrbo Xbox Horizontal
Squrbo Xbox Stacked
Squrbo Xbox Twinfan
Opus Xbox
Ecostrat
Supply & Extract
Opus 40-60-95
Opus DC
Opus Plus
XS
Squrbo
Ecosmart Squrbo Extract
Ecosmart Squrbo Supply
Xtractor
Xtractor Constant Pressure
Airmover
Squif
Twin Fans
Opus 40-60-95
Opus DC
Opus Plus
Quietscroll
Quietscroll Constant Pressure
Squif Twin
Axial Fans
Axus
Axus Bifurcated
EZPLATE
Smoke Fans
SVT Axial Impulse
SVT Centrifugl Impulse
HT Axus
HT Squif
Roof Fans
Terminator
Mark Ten

ESTCP Product Specifications

Constant Pressure Extract System
The main extract fan shall be as indicated on the drawings and in accordance with the relevant fan schedule. The vitiated air shall be extracted from the space using an energy efficient constant pressure principle via a two position motorised damper/grille installed in each area, as detailed in the schedule

Operation
The extract fan shall automatically vary its speed as the system pressure varies; the variation in pressure is caused by the opening and closing of the Nuaire NRG extract damper/grille. The damper/grille is autonomous of the fan and requires no field wiring connecting it to the fan. The damper positions are open (boost) and closed (trickle). When the damper is closed, the grille will allow approx. 8 litres/sec flow rate, as background ventilation. When open, the boost ventilation rate is between 15 and 28 litres/sec, this is in variable steps via an integral adjustment. The damper will be operated via the designated switching devices. The inline damper has an integrated balancing damper which can act as the branch volume control damper. The damper/grille shall be as manufactured by Nuaire Ltd.

(If the NRG grille is installed it shall be connected to a 12V ac supply via the inclusive 230V transformer unit and has an integral PIR, two position damper and overrun timer).

Once commissioned and set to work, the fan will maintain the preset pressure by varying its speed as the ventilation requirement within each area varies i.e. as dampers open and close. If the requirement exceeds the maximum or minimum limit, the fan will remain at the design/limiting speed.

Fan Specification
Each acoustically lined low noise Twinfan shall be fitted with an integral Ecosmart control inclusive of pressure transducer and inverter drive. The fans shall have the following energy saving and operational functions integrally installed within the fan unit, all components will be pre-wired and fitted by the manufacturer: -
  • Integral operating pressure adjustment (target pressure)
  • Maximum and minimum speed adjustment/setting.
  • Integral auto changeover/duty share, fans changeover every 12 hours of run time.
  • Auto changeover in the event of duty fan failure.
  • Volt free run & failure/status indication.
  • 4 no. low voltage sockets for interconnection of remote failure indicator.

The Fan unit shall have a 3 year warranty, first year parts and labour the remainder parts only. When the fan unit is supplied and commissioned utilising the constant pressure principle, it shall have an extended warranty. The standard warranty shall be increased from 3 to 4 years, the first year parts and labour the remainder parts only.

Fan, integrated Ecosmart controls and associated sensors/controllers shall be manufactured by Nuaire Ltd.

InstallationBy the appointed contractor.
Mechanical installation requires mounting of the extract unit in the designated position and connection to the associated duct work.

The contractor shall allow for all necessary ductwork transformations to and from the fan unit and any associated components in accordance with the manufacturers recommendations, DW 144 and general good practice.

Electrical installation requires the provision and connection of single phase electrical supply sizes 6 & 9 or three phase sizes 11 to 19 inclusive.
A volt free run/fail status indication at the fan.
A single phase supply to the duct mounted damper version NRG-IL.
A single phase supply to the transformer feeding the grille with integrated damper and PIR, the 12V output of which is connected to the grille.

Commissioning - By the appointed commissioning engineer.
The systems should be commissioned in the normal way and the operating or target pressure (inlet side of unit only) set via a potentiometer in the integral set-up box within the fan unit. This should be adjusted until the required air volume flow rate is achieved on the approved measuring device. The manufacturer’s recommendations must be observed at all times.